Single Action Pneumatic Actuator for Valve
Pickup availability could not be loaded
Single-Acting Pneumatic Valve Actuator — Fail-Safe NC or NO, ISO 5211, 15 Models PACS032 to PACS270
The single-acting pneumatic actuator is the standard automation mechanism for butterfly and ball valves in processes where fail-safe is a safety requirement — upon loss of compressed air supply or control signal, the internal mechanical spring brings the valve to a predefined position (closed or open) without reliance on active electronic components or power supply. The NC (Normally Closed) configuration closes the valve upon failure — standard for gas, steam, and hazardous fluid services. The NO (Normally Open) configuration opens the valve upon failure — standard for refrigeration, cooling, and processes where flow must be maintained during an emergency.
Available in 15 models from PACS032 to PACS270, covering butterfly and ball valves from small (2") to large (24"+) diameters with direct ISO 5211 mounting without adapters.
Single-acting vs. double-acting — when to specify each
| Criterion | Single-Acting ← This product | Double-Acting |
|---|---|---|
| Fail-safe by mechanical spring | ✅ Yes — the spring closes (NC) or opens (NO) upon air failure | ❌ No — remains in last position upon air failure |
| Process safety requirement | ✅ First choice — gas, steam, hazardous fluids | Only when the last position is the safe state |
| Compressed air consumption | Higher — the spring resists active movement | ✅ Lower — air only in the direction of movement |
| Available operating torque | Lower — the spring reduces available torque to operate the valve | ✅ Higher — all actuator torque available in both directions |
| Operating speed | Opening and closing at different speeds — the spring determines the speed in one direction | ✅ Independent speed control in both directions |
| Large valves with high torque | ⚠️ Verify net available torque vs. valve required torque | ✅ First choice for large diameter or high pressure valves |
| Relative cost | ✅ Similar — same base price, different internal configuration | Similar |
NC vs. NO — define the fail-safe position before ordering
The fail-safe position is the most important decision when specifying a single-acting actuator. It must be defined by the process risk analysis — not by operational convenience:
- Normally Closed (NC) — fail closed: The spring closes the valve when there is no air. The valve remains open while there is air supply and an open signal. Upon any failure — loss of air, compressor failure, air line break — the valve closes automatically. First choice for: natural gas and LPG (fail closed prevents leakage), hazardous or toxic fluids, chemical dosing where excess is dangerous, shut-off valves in safety systems.
- Normally Open (NO) — fail open: The spring opens the valve when there is no air. The valve remains closed while there is air supply and a close signal. Upon any failure, the valve opens automatically. First choice for: refrigeration systems where flow must be maintained (fail closed would stop cooling), safety equipment bypass, emergency cooling systems, processes where interrupting flow is more dangerous than continuing it.
The same physical valve can be configured as NC or NO — the difference is the orientation of the internal spring and the position of the control solenoid. Specify NC or NO when ordering.
Air connection — G ports and operating pressure
The recommended air supply pressure is 4 to 7 bar (58 to 100 psi). The actuator operating torque increases proportionally with supply pressure — always verify the net available torque at the minimum guaranteed pressure of the air network, not just at the maximum pressure.
Correct model selection — criteria
To select the correct PACS model for a specific valve:
- Step 1 — Valve required torque: Obtain the valve's maximum operating torque at the process's maximum differential pressure. This data is in the data sheet of each Cematic valve or can be calculated with the technical team.
- Step 2 — Minimum 1.25× safety factor: The torque of the selected actuator must be at least 1.25 times the valve's maximum torque — verify at the minimum guaranteed pressure of the air network (not at the maximum).
- Step 3 — ISO 5211 mounting: Verify that the J or K mounting of the selected model (F03, F05, F07, F10, F12, F14, F16) is compatible with the valve's ISO 5211 mount.
- Step 4 — NC or NO: Define the process fail-safe position and specify the corresponding configuration when ordering.
Cematic performs the selection of the correct actuator for each valve and process conditions combination at no additional cost. Share the valve model, diameter, maximum differential pressure, and required fail-safe position.
Compatible accessories
- 24 VDC / 110 VAC / 220 VAC control solenoid: For open/close signal from PLC or control system
- Limit switch box: Open/closed position confirmation signal to PLC — 2 microswitches or magnetic sensors
- 4–20 mA electro-pneumatic positioner: For proportional modulating control — positions the valve at any point between 0° and 90°
- Flow regulators (speed controllers): Independent opening and closing speed adjustment
- Air filter regulator: Regulation and filtration of the air supply to the actuator — recommended in all cases
Compatible Cematic valves
- ✅ Iron wafer butterfly valves — standard series and Series 200
- ✅ ANSI 150 and DIN PN16 Lug-type butterfly valves
- ✅ High-performance butterfly valves — double eccentric Class 150, 300, and 600
- ✅ PVC wafer butterfly valves
- ✅ SS316 and WCB ball valves — flanged and threaded with ISO 5211
- ✅ PFA anti-corrosive ball valves
- ✅ V-port ball valves
- ✅ Any valve with an ISO 5211 mount compatible with F03 to F16 mountings
For the double-acting actuator, see double-acting pneumatic actuator →
For valve + pneumatic actuator assemblies already assembled, see valves with pneumatic actuator →