Temperature Control Automation Kit | Pneumatic Control Valve | 4–20 mA

In stock
Regular price Solicitar precio

Automation Kit for Temperature Control in Pneumatic Control Valve

The temperature control kit for pneumatic control valve from Cematic adds process temperature monitoring and regulation to any control valve from the same product line.

In addition, the kit includes a process-threaded immersion temperature sensor, an industrial signal converter, and a programmable HMI panel with a touchscreen, all selected and validated by Cematic to operate together with the smart linear positioner and the linear-type pneumatic control valve.

What problem does the temperature control kit for control valve solve?

In industrial processes where the fluid temperature determines the opening position of the control valve, the operator needs to view that variable in real time and, therefore, act on it from a centralized point.

That is why Cematic's automation kit for temperature control addresses exactly that need: the sensor measures the temperature directly in the pipe, the converter standardizes the signal to 4–20 mA, and the HMI panel displays the value on the screen and executes the control logic on the valve's smart linear positioner.

Components of the temperature control kit for control valve

Component Cematic SKU Technical description
Temperature sensor with integrated display PCHA2313 ½" NPT process thread · Range −50…+150 °C · IO-Link 1.1 + 4–20 mA / 0–10 V analog output + 1 PNP/NPN switching output · 4-digit bicolor display · IP67 · Pt1000
IO-Link → 4–20 mA signal converter PCGE1213 IO-Link 1.1 COM2 input · 2 independent 4–20 mA analog outputs · Local display · M12 connection · 18–30 V DC · CE / cULus
5" programmable HMI panel PCHMI01 5" color touchscreen 800×480 px · ARM Dual Core 64-bit 800 MHz · 1 GB RAM · 2 GB Flash · Ethernet / CAN / USB 2.0 · CODESYS 3.5 · 8–32 V DC
M12 connection cable · 4-pin · 1 m PCC012 Straight male – straight female · Code A · PUR · IP67/IP68/IP69K · Gold-plated contacts · Silicone and halogen-free
M12 connection cable · 4-pin · 2 m PCC013 Straight male – straight female · Code A · PUR · IP67/IP68/IP69K · Gold-plated contacts · Silicone and halogen-free

It is important to note that the linear-type pneumatic control valve (globe) and the Cematic smart linear positioner are selected separately according to the nominal diameter, operating pressure, and fluid characteristics. Therefore, Cematic's technical team performs the selection engineering at no additional cost.

Connection variants of the temperature control kit

Specifically, the PCHA2313 sensor integrates two physically independent signal outputs. Therefore, the temperature control kit for control valve supports two actual connection variants according to the process requirements.

Variant 1 — IO-Link with analog converter (recommended)

First, the sensor transmits its information using the IO-Link 1.1 digital protocol. Next, the PCGE1213 converter receives the digital frame and delivers two independent 4–20 mA analog signals to the HMI panel. Therefore, this variant is recommended because it maximizes the capabilities of the sensor and the temperature control system.

Regarding the signal path, the PCC012 cable (M12 · 1 m) connects the sensor to the converter via IO-Link 1.1 COM2 at 38.4 kBaud. Then, the PCC013 cable (M12 · 2 m) carries the 4–20 mA analog signal from the converter to the PCHMI01 HMI panel.

  • Two independent 4–20 mA analog channels: for example, the converter allows connecting the HMI panel and a second receiving device simultaneously, such as a data logger or an external PID loop.
  • Extended diagnostics via IO-Link: additionally, this variant provides access to the maximum recorded temperature, switching output status, and diagnostic events from the HMI panel or from SCADA.
  • Remote parameter adjustment: it is also possible to reconfigure setpoints, alarm ranges, and analog output behavior without removing the sensor from the pipe.

Variant 2 — Direct analog signal without converter

In contrast, in this variant, the native analog output of the PCHA2313 sensor (4–20 mA or 0–10 V, programmable) is used, connected directly to the PCHMI01 HMI panel via the PCC013 cable (M12 · 2 m). This simplifies the architecture when dual channels and IO-Link diagnostics are not required.

  • Required components: in this configuration, only PCHA2313 + PCC013 + PCHMI01 are needed. Therefore, the PCGE1213 converter and the PCC012 cable are not necessary in this variant.
  • Limitation: however, IO-Link communication is lost, and with it, advanced diagnostics, remote parameter adjustment, and the converter's two independent analog channels.
  • When to apply it: for example, when the infrastructure already has conventional analog inputs and the process does not require extended sensor diagnostics.

Comparison of temperature control kit variants

Feature Variant 1 — IO-Link + converter Variant 2 — Direct analog
Transmission protocol Digital IO-Link 1.1 → 4–20 mA Native 4–20 mA or 0–10 V
Active kit components PCHA2313 + PCGE1213 + PCHMI01 PCHA2313 + PCHMI01
Required cables PCC012 (1 m) + PCC013 (2 m) PCC013 (2 m) only
Available analog channels Up to 2 independent channels 1 channel
Advanced sensor diagnostics Yes — via IO-Link Not available
Remote parameter adjustment Yes — without disconnecting the sensor No — field only
Scalability to SCADA High Medium

Technical specifications of the automation kit for temperature control

Temperature sensor — PCHA2313

  • First, its measurement range covers −50 to +150 °C (−58 to +302 °F) using a Pt1000 element (thin-film RTD).
  • In addition, the accuracy is ± 0.3 K + (± 0.1% of the span), with a display resolution of 0.1 K.
  • The process connection is via a ½" NPT thread, with a sensitive immersion length of 34.4 mm.
  • Likewise, the electrical connection is via an M12 × 1, 4-pin, straight connector.
  • Regarding the protocol, it uses IO-Link 1.1 COM2, with a user-scalable 4–20 mA or 0–10 V analog output.
  • It also includes a selectable PNP/NPN switching output, programmable NC/NO, and an integrated 4-digit alphanumeric display with red/green bicolor indication.
  • Finally, it operates with 18…32 V DC power supply, IP67 protection rating, and an ambient temperature of −25…+70 °C.

Signal converter — PCGE1213

  • First, it receives the sensor signal via IO-Link 1.1 COM2 (38.4 kBaud) through an M12 connector.
  • In addition, it delivers two independent 4–20 mA analog outputs.
  • Likewise, it includes a local display for viewing the process value in the field.
  • Its power supply is 18…30 V DC with a maximum current of 300 mA, and the body is made of polyamide (PA).
  • Finally, it has CE, cULus, EAC, and UKCA certifications, with an ambient temperature of −25…+70 °C.

Programmable HMI panel — PCHMI01

  • First, it integrates a 5" color touchscreen (800 × 480 px) with backlighting.
  • In addition, the processor is ARM Dual Core 64-bit at 800 MHz, with 1 GB RAM and 2 GB Flash storage.
  • The communication interfaces include Ethernet, CAN (CANopen / SAE J1939), and USB 2.0.
  • It also has configurable digital and analog inputs and outputs, and 8…32 V DC power supply with a typical consumption of 19 W.
  • Likewise, it is programmed using CODESYS 3.5 according to IEC 61131-3, on an embedded Linux operating system.
  • Finally, it incorporates an integrated web server for remote monitoring via Ethernet, with dimensions of 176.6 × 114.1 × 41 mm.

M12 connection cables — PCC012 and PCC013

  • Regarding length, the PCC012 measures 1 m and the PCC013 measures 2 m; both have a straight male – straight female M12 connector, 4-pin, Code A.
  • In addition, the cable material is PUR, resistant to oils, lubricants, and cable carrier chains.
  • Likewise, they work with voltage less than 250 V AC / 300 V DC and a maximum current of 4 A.
  • They also have an IP67/IP68/IP69K protection rating and gold-plated contacts.
  • On the other hand, the coupling nut is nickel-plated cast zinc with serrated anti-vibration teeth.
  • Finally, they support an ambient temperature of −25…+90 °C and are silicone and halogen-free.

Applications of the automation kit for temperature control

Indeed, the temperature control kit for control valve is compatible with any process where the fluid temperature is the variable that determines the opening position of the valve. Among the most common industries and applications are, for example, the following:

  • Chemical and petrochemical industry: for example, in reactors, heat exchangers, and corrosive or high-temperature fluid lines where the temperature conditions the opening of the control valve.
  • Food and beverage industry: likewise, it applies in pasteurization, CIP sterilization, and finished product cooling, where the valve opening percentage is regulated based on the fluid temperature.
  • Pharmaceutical industry: also in GMP-regulated processes where the temperature must be recorded and controlled within strict and traceable limits.
  • HVAC and industrial cooling systems: likewise, in chilled water circuits, process water, and machinery cooling where the return temperature determines the opening of the control valve.
  • Power and steam generation: on the other hand, the kit applies to control in saturated steam lines, boiler feedwater, and condensate circuits.
  • Manufacturing and automotive: likewise, in the temperature of cutting fluids, hydraulic oils, and cooling circuits of production equipment.
  • Water and effluent treatment: finally, in physical-chemical and biological treatment processes where the temperature directly influences the reaction kinetics.

Benefits of the Cematic automation kit for temperature control

  • Integrated process control: above all, the fluid temperature and the opening percentage of the control valve are managed from a single HMI panel, which simplifies operation and reduces the risk of human error.
  • Simultaneous local and remote visualization: the sensor displays the temperature in the field through its integrated bicolor display. In addition, the HMI panel with Ethernet web server allows remote monitoring from any device on the plant network.
  • Predictive diagnostics: also, the IO-Link communication allows access to sensor diagnostic data and detecting anomalous temperature trends before they become process failures.
  • High environmental resistance: likewise, the connection cables have IP67/IP68/IP69K protection, gold-plated contacts, and oil-resistant PUR material, which guarantees reliability in harsh industrial environments.
  • Open and scalable architecture: on the other hand, the 4–20 mA signals and Ethernet and CAN protocols allow integration with existing SCADA, DCS, or PLC systems in the plant without additional modifications.
  • Validated Cematic solution: finally, all components of the kit have been selected and documented by the Cematic technical team, which eliminates the need for integration engineering by the end customer.

For inquiries about the kit's compatibility with your pneumatic control valve or about the selection of the smart linear positioner, contact us via WhatsApp, phone, or email. In any case, the Cematic technical team supports you at no cost in the complete configuration of the system.